Notice:Please note enclosed or open type when placing order.
	
Normal working conditions and installation conditions:
Temperature: -5°C ~ +40°C, average temperature not exceed +35°C in 24 hours.
Altitude: Do not exceed 2000m.
Air Condition: Atmospheric relative humidity can’t exceed 50% at ambient air temperature of +40℃,and the higher relative humidity may be allowed at lower temperatures. For example, when the ambient air degree is 20℃, the relative humidity can reach 90%. Because of the occasional condensation
phenomenon of the product due to the temperature changes, the user should take special protective measures.
Pollution Grade: Grade 3.
Installation category:III Class.
Mounting Condition: The inclination between the mounting plane and the vertical plane shall not exceed ±5°.
Impact shock: The product shall be installed and operated at a place without obvious shake, impact and vibration.
	
 
Main parameter and technical characteristic:
| Model | Rated Insulated Voltage Ui (V) | Ie under Intermittent Duty (A) | Max. Power of Motor can be controlled(kW) | Thermal Overload Relay | Model Specification of AC contactor | ||||||
| 380V | 660V | 220V | 380V | 660V | Type | 
					 
					Setting Current 
				 
					 Range 
				 
					 | Y Operate KM1 | Operate KM3 | Isolation with KM2 | ||
| QJX2-09 | 690 | 09 | 09 | 4 | 7.5 | 10 | JR28-13 | 7-10 | CJX2-0910 | CJX2-0901 | CJX2-0910 | 
| QJX2-12 | 12 | 8.9 | 5.5 | 11 | 13 | JR28-13 | 9-13 | CJX2-0910 | CJX2-1201 | CJX2-1210 | |
| QJX2-18 | 18 | 10.6 | 7.5 | 15 | 18.5 | JR28-13 | 12-18 | CJX2-1210 | CJX2-1801 | CJX2-1810 | |
| QJX2-25 | 25 | 18 | 11 | 18.5 | 25 | JR28-13 | 17-25 | CJX2-1810 | CJX2-2501 | CJX2-2510 | |
| QJX2-32 | 32 | 21 | 15 | 25 | 33 | JR28-13 | 23-32 | CJX2-1810 | CJX2-3201 | CJX2-3210 | |
| QJX2-40 | 40 | 34 | 18.5 | 33 | 50 | JR28-33 | 30-40 | CJX2-2510 | CJX2-4011 | CJX2-4011 | |
| QJX2-50 | 50 | 39 | 25 | 45 | 63 | JR28-33 | 37-50 | CJX2-4011 | CJX2-5011 | CJX2-5011 | |
| QJX2-65 | 65 | 42 | 30 | 55 | 63 | JR28-33 | 48-65 | CJX2-4011 | CJX2-6511 | CJX2-6511 | |
| QJX2-80 | 80 | 49 | 37 | 63 | 80 | JR28-33 | 63-80 | CJX2-5011 | CJX2-8011 | CJX2-8011 | |
| QJX2-95 | 95 | 49 | 45 | 80 | 80 | JR28-33 | 80-93 | CJX2-6511 | CJX2-9511 | CJX2-9511 | |
	
 
Outline and installation dimension:
QJX2-09~32 Open type:
	 
 
| Model | QJX2-09 | QJX2-12 | QJX2-18 | QJX2-25 | QJX2-32 | 
| A | 140 | 140 | 140 | 174 | 174 | 
| C | 140 | 149 | 154 | 164 | 169 | 
	
 
QJX2-09~32 Enclosed type:
	 
 
	
| Model | QJX2-09 | QJX2-12 | QJX2-18 | QJX2-25 | QJX2-32 | 
| A | 370 | ||||
| B | 235 | ||||
| C | 102 | ||||