AOV2 ME10

AOV2

Characteristics

AOV2, AOV3 series motor protection circuit breaker ( the following refer to as circuit breaker) is suitable for AC 50/60HZ, rated voltage 690V, rated current 80A in circuit. Three-phase squirrel cage induction motor overload, short circuit, open phase protection and not frequent starting control purposes, can be used for power distribution line protection and not frequent load conversation, also can be used as an isolator.

An overview of the product:

Design features:

● Adjustable current setting value: it can be adjusted to the appropriate current value indicating position according to the actual working current.

● Can simulate mechanism trip design: through the TEST can make the mechanism trip, convenient simulation TEST.

● Front laser engraving: the engraving logo is clearing durable.


Structural features:

● Double new point structure: double break point of contact can suppress and disperse arc energy, improve the effort of eliminating isolated, improve the ability of connecting new points, reduce the electrical loss of melting head, and effectively improve the electrical life of the product. 

● Thermal and magnetic comprehensive protection structure: the product has multiple protection functions of overload, short circuit and three-phase unbalanced.


Confirm to the standard:

● GB/T 14048.1 low-voltage switchgear and control equipment part 1 : general provisions

● GB/T 14048.2 low-voltage switchgear and control equipment circuit breakers

● GB/T 14048.4 low-voltage switchgear and control equipment part 4-1: contactors and motor starters, electromechanical contactors, and motor starter protectors (including motor protectors)

● GB/T 14048.5 low-voltage switchgear and control equipment part 5-1: control circuit appliances and switching elements, electromechanical control circuit appliances


Model specification:


Technical parameters:

AOV2-ME&PM50/60Hz,AC-3


Setting range current of
 thermal overload release


Magnetic release current

Id±20%

lt he current

with casing

Model

(the button control)

Weight

The three-phase motor standard rated power

230V

KW

400V

KW

415V

KW

440V

KW

A

A

A

A

Kg

-

-

-

-

0.1-0.16

1.5

0.16

AOV2-●●01

0.260

-

-

-

-

0.16-0.25

2.4

0.25

AOV2-●●02

0.260

-

-

-

-

0.25-0.4

5

0.40

AOV2-●●03

0.260

-

-

-

-

0.40-0.63

8

0.63

AOV2-●●04

0.260

-

-

-

0.37

0.63-1

13

1

AOV2-●●05

0.260

-

0.37

-

0.55

1-1.6

22.5

1.6

AOV2-●●06

0.260

0.37

0.75

0.75

1.1

1.6-2.5

33.5

2.5

AOV2-●●07

0.260

0.75

1.5

1.5

1.5

2.5-4

51

4

AOV2-●●08

0.260

1.1

2.2

2.2

3

4-6.3

78

6.3

AOV2-●●10

0.260

2.2

4

4

4

6-10

138

9

AOV2-●●14

0.260

3

5.5

5.5

7.5

9-14

170

13

AOV2-●●16

0.260

4

7.5

9

9

13-18

223

17

AOV2-●●20

0.260

5.5

11

11

11

17-23

327

21

AOV2-●●21

0.260

5.5

11

11

11

20-25

327

23

AOV2-●●22

0.260

7.5

15

15

15

24-32

416

24

AOV2-●●32

0.260

Breaking capacity parameter:

The breaking capacity of AOV2-ME & PM

Circuit breaker model

AOV2-ME&PM 

 

01~06

07

08

10

14

16

20

21

22

32

Rated value

A

0.1~0.6

2.5

4

6.3

10

14

18

23

25

32

The breaking capacity meets GB/T140482 Standard

230/240V

Icu

kA

lsc%(1)

 

400/415V

Icu

kA

100

100

100

100

100

lsc%(1)

 

50

50

40

40

40

440V

Icu

kA

50

20

20

20

20

lsc%(1)

 

75

75

75

75

75

500V

Icu

kA

50

42

10

10

10

10

lsc%(1)

 

100

100

75

75

75

75

Circuit breaker model

AOV2-ME&PM

 

01~06

07

08

10

14

16

20

21

22

32

Rated current

A

01~1.6

2.5

4

6.3

10

14

18

23

25

32

Thermal stress protection of cable in short circuit Minimum protective wear area

1mm2

 

≤10kA

≤6kA

(2)

(2)

(2)

(2)

(2)

(PVCInsulated copper core cable)

 

1.5 mm2

 

≤20kA

≤10kA

(2)

(2)

(2)

(2)

(2)


40°C
Isc value


2.5 mm2

 

(2)

4~6 mm2

 

★>100kA
(1) percentage of lcu

●The cable section is protected.

(2)The cable section is unprotected.


Outline dimensional diagram(mm):


a b c
AOV2-ME&PM  
44.5  
89 ME:78,PM:90 
AOV3-ME 
61.2 
121 114

(1)X1 is electrical clearance = 400mm, applicable to Ue<690v

Note:The product can be installed vertically or horizontally.Pleaseuse TH35-7.5 standard mounting guide to install.



If you have any enquiry about quotation or cooperation,please feel free to email us ator use the following enquiry form. Our sales representative will contact you within 24 hours. Thank you for your interest in our products.