Characteristics

AOU surge protect Device, also known as lightning protector. It is an electronic device that provides safety protection for various electronic equipment, instruments and communication lines. When the electrical circuit or communication line suddenly produces a peak current or voltage due to external interference, the surge protection device can lead to shunt in a very short time, in order to avoid damage to other equipment in the circuit caused by the surge.AOU surge protector device is suitable for ac 50/60 Hz power supply system with rated voltage 220V/380V to protect indirect and direct lightning effects or other transient overvoltage surges. It meets the requirements of surge protection for residential use, tertiary and industrial fields.

Main Function:Protection of instantaneous overvoltage surge

Standards:GB 18802.1、IEC 61643-1

Product Selection:


Technical Parameter:

Type

AOU-15

AOU-20

AOU-40

AOU-65

Nominal Discharge Current(kA)  In

20

10

20

30

Max Discharge Current(kA)  Imax

15

20

40

65

Max. Permissible Strength

of Backup Fuse(A)     gL

50A

50

100

125

Max Continuous Operating Voltage(V)           Uc

275

340

385

440

275

340

385

440

275

340

385

440

275

340

385

440

Protection Level(kV)   Up

1.7

1.8

2.0

2.2

1.3

1.5

1.6

1.8

1.5

1.8

1.8

2.0

1.6

1.9

2.0

2.2

Protection Class       μs

Level 1 Protection

+

Level 2 Protection

Level 2 Protection

Waveform           μs

8/20 and 10/350

8/20

Leakage Current 75%Uc 1mA                μA    

≤20

Response Time        ns

≤25

ProductStructure

Plug

Protection Method

Protection of Incoming Line

Pole

1P,2P,3P,4P,1P+N,3P+N

Working Condition Indicator Window

Yes (Green: Normal, Red: Fault)

Wiring Capacity of Terminal

Minimum Size of Copper Conductor 4mm, Maximum Size: Unistrand 36mm, Multistrand 25mm2

Standards

IEC61643-1、GB18802.1

Optional Accessories

Yes (YX telecommand)

Installation

It is modular construction which can directly install at the standard DIN rail. Rated Torque: 3.5NM

Protection Level

Ip20

  

Accessory

YX Telecommand

 

Rated Operational Voltage       Ue

125V

Rated Operating Current         Le

1A

Contact

One normally open contact, one normally closed contact.

Function

When SPD module fails and disconnects, normally open contacts will close and normally closed contacts will break. A fault message will be sent.


Outline Overall and Installation Dimensions:

Speciflcations

Width (mm)

1P

18

2P/1P+N

36

3P

54

4P/3P+N

72

AOU-15~65 Surge Protection Device