AOLR-80 3P+N Residual Current Circuit Breaker

AOLR-80

صفات

AOLR series residual current operated circuit breakers are used in low-voltage terminal power distribution systems in the fields of industry, civil buildings, energy, communications, and infrastructure. They have short-circuit, leakage protection, and isolation functions. They provide personal protection for indirect contact and supplementary for direct contact. Protection, to provide protection against insulation failures of electrical equipment.

Product Selection:

Technical Parameters:

Type

AOLR-80

Standard

IEC61009-1,GB16917.1,IEC61008-1,GB16916.1

Functions

Leakage Protection、Short Circuit Protection Function、Isolation Function

Frame Current(A)

100

Pole

2(1+N)、4(3+N)

Rated Current(A)

16、20、25、32、40、63、80

Rated Voltage(V)

AC230(1P)、AC230/400

Insulation Voltage

500

Rated Impulse Withstand Voltage(KV)

4

Rated Residual Working Current(mA)

30、100、300

Residual Current Characteristics

A型、AC型

Rated Short-Circuit Breaking Capacity

6KA

Rated Ultimate Short Circuit Breaking Capacity

6KA

Rated Opetating Short-Circuit Breaking Capacity

6KA

Max.Breaking Capacity at Rated Residual Current

0.1s

Trip Curve

-

Release Form

Thermomagnetic Release

Electrical Life

10000

Mechanical Life

20000

Pollution Grade

2

Protection Level

IP20

Temperature

-35℃~ +70℃

Altitude

Do not Exceed 2000m

Wiring Terminal 

Screw Crimping

Max. Connection Capacity (m㎡)

25

Max.Ultimate Torque (Nm)

2.5

Installation Category

II、III

Installation Method

TH35-7.5 Standard DIN rail

lncoming Wiring Method

Installed the Wire at the Top


Outline Overall and Installation Dimensions (mm):